Setup Causes UPS to Switch to Battery Mode (127083)
The information in this article applies to:
This article was previously published under Q127083 SYMPTOMS
When you install Windows 95 on a computer with an uninterruptible power
supply (UPS) attached to a serial port, the UPS switches to battery mode
during the hardware detection portion of Setup. If Setup does not finish
before the battery in the UPS runs out, the UPS shuts down and the computer
restarts.
CAUSE
The hardware detection portion of Setup attempts to detect the computer's
serial ports. The method that Setup uses to query the serial ports can
cause some serial-port-monitoring UPS models to believe that the external
power has failed.
RESOLUTION
Disconnect the UPS monitoring cable from the serial port before you run
Windows 95 Setup.